SLDs Not Displaying Properly

Occasionally, PTW might display an SLD forced into one corner or one edge of the available area (even when View>>Zoom All has been used). This is probably because the project was imported from V3.8 and that version has caused a slight problem in remembering invisible datablocks or textblocks. There are a number of possible solutions to your problem.

Display hidden datablocks
Edit>>Select All followed by OneLine>>Datablocks>>Visible. The problem might be caused by PTW trying to display an invisible datablock that has been accidentally moved far away from its component. The solution is to simply move the errant datablock closer to its component.

Display hidden nametags
Edit>>Select All followed by OneLine>>Nametags>>Visible. This is for the same reason as for the datablocks above.

Copy the components to another SLD
If you "mouse around" the visible components and click on Edit>>Copy. Then open a new SLD (Document>>OneLine....New) and paste (Edit>>Paste) the components into the new drawing. Do not use Edit>>Select All before copying because you might select a problem textblock.

Recreate the SLD on another drawing
This will definitely solve your problem, but might take you longer than the previous steps. Create a new SLD (Document>>OneLine....New), insert the main busbar onto the drawing (Component>>Existing) and expand this up (Component>>Expand) to recreate your network again. This will involve re-spacing your drawing.

 

 