CEE Relays Ltd.

87C Whitby Road, Slough, SL1 3DR

Telephone: +44 1753 576477        Fax: +44 1753 825661

Website: www.ceerelays.co.uk

 

 

 

DAPPER Studies

DAPPER is an integrated set of modules for three-phase power system design and analysis including rigorous load flow and voltage drop calculations, impact motor starting, traditional fault analysis, demand and design load analysis, feeder, raceway and transformer sizing, and panel, MCC, and switchboard schedule specification.

Benefits:

bullet Generate better designs by comparing alternatives quickly.
bullet Improve accuracy with DAPPER’s rigorous solution methods.
bullet Save time by sharing a common project database and interface.
bullet Improve consistency with standard design libraries.
bullet Design safer systems by comparing calculations with short circuit and continuous ratings.
bullet Communicate designs effectively with presentation quality graphics, reports, and equipment schedules.

LOAD FLOW/VOLTAGE DROP:

With DAPPER, users can calculate the voltage drop on each feeder and transformer branch, voltage on each bus, projected power flow, and losses in the power system.

This program may be used for conventional voltage drop analysis, loss analysis, power factor studies, capacitor placement, long-line charging effects, impact loading for motor starting studies, generator sizing, and for cogeneration analysis. With DAPPER, a single load flow program models loop and radial power systems. Double precision sparse matrix current injection solutions are used for faster, more accurate conver-gence. This allows for better modeling of ill-conditioned systems.

Features:

bullet Models radial, loop, and multiple independent systems.
bullet Models utility and generator equivalent impedance calculated from short circuit duty.
bullet Models up to 50 utilities/swing bus generators.
bullet Models up to 400 regulated and unregulated co-generators.
bullet User definable per unit driving voltage at each utility and swing bus generator.
bullet Models transformer primary and secondary taps and off nominal rated voltages.
bullet Full transmission line modeling with built in line parameter calculators.
bullet Models any combination of motor and non-motor loads with global and/or local load factors.
bullet Models any combination of constant kVA, constant impedance and constant current loads.
bullet Reports bus voltage, voltage angle, and voltage drop at each bus.
bullet Reports branch voltage drop, power flow in kW, kVAR, kVA, Amps and power factor.
bullet Reports branch loss in kW, kVAR, kVA, and total system losses.
bullet User definable report criteria for bus and branch voltage drops.
bullet Percentage voltage drops based on system voltage per ANSI standards.
bullet Double precision calculations improve solution accuracy.
bullet Rapid solution convergence.
bullet Suitable for impact motor starting, capacitor placement and power factor studies.
bullet Load flow results validated to match with benchmark calculations and IEEE examples.

COMPREHENSIVE FAULT ANALYSIS:

The DAPPER Comprehensive Fault Analysis program provides a network solution of three-phase, phase-earth, phase-phase, and phase-phase-earth fault currents; RMS momentary fault currents; asymmetrical fault duties at three, five, and eight cycles; the positive, negative, and zero sequence impedance values between each fault location, and contributions from utilities, generators, and motors. At each fault location, the direction, X/R, and magnitude of fault currents are reported, thus providing a clear view of the conditions that exist during the fault.

Features:

bullet Symmetrical and Asymmetrical values reported at 1/2, 3, 5, and 8 cycles.
bullet Asymmetrical values reported at user selected fault time.
bullet Asymmetrical values reported as peak or RMS values.
bullet Models two-winding and three-winding transformer taps, phase shift, and off-nominal rated voltages.
bullet Asymmetrical exponential DC decay is based on X/R to each contribution.
bullet Reports Thevenin equivalent impedance and X/R at the faulted bus.
bullet Detailed and summary reporting options.
bullet Reports bus voltages and branch flows throughout the system for each faulted bus.
bullet Reports phase or sequence current and voltage.
bullet Reports ground return current for double line to ground faults.
bullet Models transformer and generator neutral grounding impedances.

DEMAND LOAD ANALYSIS:

Features:

bullet Reports Connected, Demand, and Design loads.
bullet All load calculations account for individual load power factors.
bullet Automatically creates input load data for Load Flow and Voltage Drop Studies.
bullet Automatically creates loads for sizing feeders and transformers.
bullet System demand loads calculated using methods recognized by the NEC.
bullet Automatically tracks largest motor fed by each bus to meet NEC requirements.
bullet Automatic compliance with NEC and local codes for multi-level load diversity.
bullet Sensitivity studies, future load growth studies and load diversity studies by scaling load factors globally.
bullet "What if" analysis of loading conditions, for example light loading versus normal loading, or winter versus summer loading.
bullet Meet utility company requirements for providing a load summary by load type for connected, demand, and design loads at each utility bus.
bullet Generate sufficient information for sizing feeders, transformers, and other elements of the power system.

FEEDER AND TRANSFORMER SIZING:

DAPPER will size feeder cables, ground wires, raceways, bus ducts, duct banks and transformers throughout the power system to the load requirements calculated by the Demand Load Analysis program. Feeders are selected to meet user-defined criteria for conductor material, voltage level, insulation type, and environmental conditions. Transformer primary and secondary feeders are sized to the transformer full load as specified by the user. Feeders and transformers may be included, excluded or evaluated in the sizing study.

Features:

bullet AWG, Bus Duct, ACSR, or metric sizes may be used.
bullet Feeders and transformers with "Do Not Size" are evaluated for capacity.
bullet Feeder libraries permit user to include metric sizes and ampacity.
bullet Transformers can be sized to Demand or Design load.
bullet Sizing to the IEE wiring regulations is available.

LOAD SCHEDULES:

The DAPPER Load Schedule module provides detailed documentation of load fed through Panels, Motor Control Centers (MCCs) and Switchboards. Input is simplified through the use of libraries and copy and paste functions. The schedules can be displayed, printed, and exported in a variety of different formats.

Features:

bullet Schedules are automatically updated with available short circuit values and sub-feed totals.
bullet Switch board schedules are automatically generated from connected branch loads.
bullet

MCC schedules can reference a default design library for automatic selection of feeder and raceway sizes, or the complete cable library for more detailed specification.

 

Download the brochure in PDF format:

 

      PTW_DAPPER.pdf (1.3MB)

 

Download Acrobat Reader - version 5.0 (or above) required.


Copyright © 2002-2008 CEE Relays Ltd.

 

[ Home ]

[ Contact Us ] [ FAQs ] [ PTW FAQs ] [ Download ]